Key specifications at a glance

  • Connection: three-phase (3P4W, 3P3W) or single-phase (1P2W) network, CT-connected, 1 A or 5 A secondary; 0.05–5(6) A
  • Accuracy class: Class B or C (EN 50470-3:2022); Class 1 (IEC 62053-21) or Class 0.5S (IEC 62053-22)
  • MID: module B+D, certificate number 0120/SGS0703 according to the datasheet; the 333 mV -MV version is not MID; the MID-certified version is confirmed with the quote
  • Communication: RS485 Modbus RTU (SDM630MCT), M-Bus (SDM630MCT-MB); 2 pulse outputs
  • Measured quantities: bidirectional kW and kWh; kvarh, var, VA, V, A, PF, THD, Hz, max demand
  • Width: 4 DIN modules (72 mm)

Applications

  • Metering of higher-current industrial main feeders and branch circuits through current transformers
  • Monitoring of energy consumption and electrical parameters
  • EV charging energy metering
  • MID-certified submetering at CT-connected metering points

Eastron SDM630MCT models

Eastron SDM630MCT models
Model Rating Distinguishing feature
SDM630MCT three-phase, CT-connected 1 A / 5 A, 3 × 230/400 V RS485 Modbus RTU
SDM630MCT-MB three-phase, CT-connected 1 A / 5 A, 3 × 230/400 V M-Bus (EN 13757-3)

Technical specifications – CT-connected Modbus energy meter

Technical specifications – CT-connected Modbus energy meter
Parameter Value
Connection three-phase (3P4W, 3P3W) or single-phase (1P2W) network, CT-connected, 1 A or 5 A secondary
Nominal voltage 3 × 230/400 V AC
Voltage range 100–277 V AC (L-N), 100–480 V AC (L-L)
Frequency 50/60 Hz; range 45–65 Hz
Current 0.05–5(6) A
Starting current 5 mA
CT primary current 1–9,999 A (configurable)
VT setting secondary voltage 100–500 V; ratio 1–9,999
Overcurrent withstand 20 × Imax for 0.5 s
Power consumption ≤ 2 W / 10 VA per phase
Insulation 4 kV AC for 1 minute; impulse 6 kV (1.2/50 µs)
Auxiliary supply from a separate AC auxiliary supply or, where appropriate, from the monitored supply
Active energy accuracy Class B or C (EN 50470-3:2022); Class 1 (IEC 62053-21) or Class 0.5S (IEC 62053-22)
Reactive energy accuracy Class 2 (IEC 62053-23)
Accuracy of instantaneous values voltage and current ±0.5%, frequency ±0.2%, power factor ±0.01, active, reactive and apparent power ±1%
Max reading 9,999,999.9 kWh or kvarh
Demand integration period max 60 minutes
Pulse outputs 2 passive outputs; output 2 fixed at 3,200 imp/kWh, 100 ms; output 1 configurable, pulse width 200, 100 or 60 ms
RS485 Modbus RTU – SDM630MCT 2,400–38,400 bps; address 1–247; max 64 devices per bus; max 1,000 m
M-Bus – SDM630MCT-MB EN 13757-3; 600–9,600 bps; primary address 1–250; secondary address 00 00 00 01–99 99 99 99
Ingress protection IP51 front panel, IP20 whole meter
Operating temperature −40 to +70 °C
Storage temperature −40 to +80 °C
Relative humidity operating ≤ 90%, storage ≤ 95%, non-condensing
Installation environment overvoltage and installation category CAT III; protective class II; mechanical environment M1, electromagnetic environment E2; pollution degree 2; altitude max 2,000 m
Dimensions (W × H × D) 72 × 94.5 × 65 mm; 35 mm DIN rail
Wire size 0.5–2.5 mm², M3, 0.2 Nm (all terminals)
Compliance EMC: EN 61326-1:2021, EN 61326-2-3:2021, EN IEC 62052-11:2021/A11:2022; Low Voltage Directive: EN 61010-1:2010+A1:2019, EN IEC 61010-2-030:2021+A11:2021, IEC 62052-31:2015; MID standard: EN 50470-3:2022

Source: Eastron SDM630MCT (MID) series datasheet (July 2025), SDM630MCT Series user manual (2024 V1.1, November 2024), manufacturer product page and EV charging metering application page (as of November 2026). Specifications are subject to change by the manufacturer.

How to choose

Current transformers and measuring range

The SDM630MCT works with current transformers rated 1 A or 5 A secondary; the CT primary current is set on the meter between 1 and 9,999 A. Size the CTs to the highest expected current, because an oversized CT reduces accuracy at low load. For circuits up to 100 A, the direct-connected Eastron SDM630 is the simpler option.

Communication

For a monitoring platform or an energy management system (EMS), the SDM630MCT connects over RS485 Modbus RTU, with up to 64 devices per bus and cable runs up to 1,000 m. The SDM630MCT-MB fits M-Bus meter reading networks. Both models have 2 pulse outputs.

MID-certified metering

If the application requires certified metering, for example because energy is billed to a third party, choose a MID-certified version. The Eastron series datasheet states module B+D; the SDM630MCT-MV version (333 mV input) is not MID. Please indicate in your quote request if you need a MID-certified meter, and we will confirm the version and order code.

VT metering and auxiliary supply

For metering through voltage transformers, the VT secondary voltage (100–500 V) and ratio (1–9,999) can be set on the meter. The meter is powered from a separate AC auxiliary supply or, where appropriate, from the monitored supply.

Rogowski coil alternative

Where a 0.5–10 kA main feeder is to be measured with Rogowski coils, the Eastron SDM630MCT-RC series is the option to consider.

Related services and products

Energom Electronic Kft. is an official distributor of Eastron. Services across the Central and Eastern European region; product delivery across Europe. For SDM630MCT projects, Energom designs the metering chain from the current transformers to the monitoring platform, handles installation and commissioning, and integrates the meters with your energy management system.

FAQ

Which current transformers work with the Eastron SDM630MCT?

The SDM630MCT works with current transformers rated 1 A or 5 A secondary, with a meter-side current range of 0.05–5(6) A. The CT primary current is set on the meter between 1 and 9,999 A.

Does the Eastron SDM630MCT have MID certification?

The Eastron SDM630MCT series datasheet states MID module B+D (certificate number 0120/SGS0703); the 333 mV SDM630MCT-MV version is not MID. The MID-certified version and its order code are confirmed with the quote; active energy accuracy is Class B or C (EN 50470-3:2022).

How accurate is the SDM630MCT?

The Eastron SDM630MCT measures active energy to Class 1 (IEC 62053-21) or Class 0.5S (IEC 62053-22), and Class B or C (EN 50470-3:2022); reactive energy is Class 2 (IEC 62053-23). Instantaneous voltage and current are accurate to ±0.5%.

Can the SDM630MCT be used for EV charging metering?

Eastron lists the SDM630MCT among its meters for EV charging energy metering. Bidirectional measurement and the Modbus link let the metered data flow into the monitoring system.

Does the SDM630MCT need an auxiliary supply?

The SDM630MCT is powered either from a separate AC auxiliary supply or, where appropriate, from the monitored supply.