Eastron SDM630 100 A Three-Phase DIN Rail Energy Meter
The Eastron SDM630 is a three-phase, direct-connected DIN rail energy meter family (submeter) for 3 × 230/400 V networks, rated up to 10(100) A and four DIN modules (72 mm) wide. The meters measure energy bidirectionally and come in RS485 Modbus RTU (SDM630-M, SDM630-Modbus V2), M-Bus (SDM630-MB) and pulse-output-only (SDM630-P) versions.
Key specifications at a glance
- Connection: three-phase (3P4W, 3P3W) or single-phase (1P2W) network, direct, 0.3–10(100) A; SDM630-Modbus V2: 0.5–10(100) A; 3 × 230/400 V
- Accuracy class: Class B or C (EN 50470-3:2022), Class 1 or 0.5 (IEC 62053-21); SDM630-Modbus V2: Class 1 (IEC 62053-21)
- MID (Energom statement, not manufacturer data): among the direct meters only the SDM630-M is MID-certified (module B+D); the SDM630-Modbus V2 has no MID
- Communication: RS485 Modbus RTU (SDM630-M, SDM630-Modbus V2), M-Bus (SDM630-MB), pulse only (SDM630-P); 2 pulse outputs
- Measured quantities: bidirectional kW and kWh; kvarh, var, VA, V, A, PF, THD, Hz, max demand
- Width: 4 DIN modules (72 mm)
Applications
- Submetering of three-phase loads and feeders, direct connection up to 100 A
- Monitoring of energy consumption and electrical parameters (voltage, current, power factor, THD) over Modbus or M-Bus networks
- Bidirectional energy metering where import and export must be registered separately
- MID-certified submetering with the SDM630-M (per Energom)
Eastron SDM630 models
| Model | Rating | Distinguishing feature |
|---|---|---|
| SDM630-M | three-phase, 0.3–10(100) A, 3 × 230/400 V | RS485 Modbus RTU; available MID-certified (module B+D) |
| SDM630-MB | three-phase, 0.3–10(100) A, 3 × 230/400 V | M-Bus (EN 13757-3) |
| SDM630-P | three-phase, 0.3–10(100) A, 3 × 230/400 V | pulse output only |
| SDM630-Modbus V2 | three-phase, 0.5–10(100) A, 3 × 230/400 V | RS485 Modbus RTU; Class 1 (IEC 62053-21) |
According to Energom, the SDM630-M is the only MID-certified direct meter in the range; the SDM630-Modbus V2 has no MID.
Technical specifications – three-phase DIN rail energy meter
| Parameter | Value |
|---|---|
| Connection | three-phase (3P4W, 3P3W) or single-phase (1P2W) network, direct |
| Nominal voltage | 3 × 230/400 V |
| Voltage range | SDM630-M, -MB, -P: 100–277 V AC (L-N), 100–480 V AC (L-L); SDM630-Modbus V2: 100–276 V AC (L-N), 173–480 V AC (L-L) |
| Frequency – SDM630-M, -MB, -P | 50/60 Hz |
| Current | 0.3–10(100) A; SDM630-Modbus V2: 0.5–10(100) A |
| Starting current | 40 mA |
| Transition current (Itr) – SDM630-M | 1 A |
| Overcurrent withstand – SDM630-M, -MB, -P | 30 × Imax for 0.01 s |
| Power consumption – SDM630-M | voltage circuit ≤ 2 W / 10 VA per phase; current circuit ≤ 0.05 VA |
| Insulation – SDM630-M, -MB, -P | 4 kV AC for 1 minute; impulse 6 kV (1.2/50 µs) |
| Active energy accuracy | Class B or C (EN 50470-3:2022), Class 1 or 0.5 (IEC 62053-21); SDM630-Modbus V2: Class 1 (IEC 62053-21) |
| Reactive energy accuracy | Class 2 (IEC 62053-23) |
| Accuracy of instantaneous values | voltage and current ±0.5%, frequency ±0.2%, power factor ±0.01, active, reactive and apparent power ±1% |
| Max reading | 999,999.99 kWh or kvarh |
| Demand integration period | max 60 minutes |
| Pulse outputs | 2 passive optocoupler outputs; output 2 fixed at 400 imp/kWh, 100 ms; output 1 configurable (total, import or export kWh or kvarh), pulse width 200, 100 or 60 ms |
| Pulse output external supply – SDM630-M | 5–27 V DC, max 27 mA |
| RS485 Modbus RTU – SDM630-M and SDM630-Modbus V2 | 2,400–38,400 bps; address 1–247; max 1,000 m; SDM630-M: max 64 devices per bus |
| M-Bus – SDM630-MB | EN 13757-3; 600–9,600 bps; primary address 1–250; secondary address 00 00 00 01–99 99 99 99 |
| Ingress protection – SDM630-M, -MB, -P | IP51 front panel, IP20 whole meter (IEC 60529) |
| Operating temperature | SDM630-M, -MB, -P: −40 to +70 °C; SDM630-Modbus V2: −25 to +55 °C (optionally −40 to +70 °C) |
| Storage temperature | SDM630-M, -MB, -P: −40 to +80 °C; SDM630-Modbus V2: −40 to +70 °C |
| Relative humidity | operating ≤ 90%, storage ≤ 95%, non-condensing; SDM630-Modbus V2: 0–90% |
| Vibration | 10–50 Hz (IEC 60068-2-6) |
| Installation environment – SDM630-M, -MB, -P | overvoltage and installation category CAT III; protective class II; mechanical environment M1, electromagnetic environment E2; pollution degree 2; altitude max 2,000 m |
| Dimensions (W × H × D) – SDM630-M, -MB, -P | 72 × 100 × 66 mm; 35 mm DIN rail |
| Weight – SDM630-M | approx. 325 g |
| Wire size | SDM630-M: main terminals 4–25 mm², M5, 3.5 Nm; signal terminals 0.5–1.5 mm², M2.5, 0.4 Nm; SDM630-Modbus V2: voltage inputs up to 25 mm² |
| Emissions – SDM630-M | EN 55032 Class B (radiated and conducted) |
| Compliance – SDM630-M, -MB, -P | EMC: EN 61326-1:2021, EN 61326-2-3:2021, EN IEC 62052-11:2021/A11:2022; Low Voltage Directive: EN 61010-1:2010+A1:2019, EN IEC 61010-2-030:2021+A11:2021, IEC 62052-31:2015; active energy metering: EN 50470-3:2022 |
Source: Eastron SDM630 series datasheet (July 2025), SDM630-M user manual (2025 V1.01, November 2025), SDM630-Modbus V2 user manual (2023 V1.5) and manufacturer product pages (as of November 2026). MID status per Energom. Specifications are subject to change by the manufacturer.
How to choose
MID-certified billing or internal submetering
If the application requires certified metering, for example because energy is billed to a third party, choose a MID-certified meter. According to Energom, the SDM630-M is the only MID-certified direct meter in the range (module B+D); the SDM630-Modbus V2 has no MID. For internal cost allocation and monitoring, the V2 also works, with Class 1 accuracy (IEC 62053-21).
Communication
For a monitoring platform or an energy management system (EMS), the SDM630-M and SDM630-Modbus V2 connect over RS485 Modbus RTU, with cable runs up to 1,000 m; the SDM630-M supports up to 64 devices per bus. The SDM630-MB fits M-Bus meter reading networks, and the SDM630-P is enough for pulse counting.
Current and connection
The SDM630 is a direct-connected meter rated up to 10(100) A, suitable for three-phase four-wire, three-phase three-wire and single-phase two-wire networks. Main feeders above 100 A need a CT-connected meter, such as the Eastron SDM630MCT, or for 0.5–10 kA main feeders the Rogowski coil SDM630MCT-RC.
Installation environment
The SDM630-M, -MB and -P operate from −40 to +70 °C; the standard SDM630-Modbus V2 operates from −25 to +55 °C. The SDM630-M, -MB and -P are rated IP51 at the front panel and IP20 for the whole meter, so they belong inside a distribution board.
Related services and products
- Energy meters and current transformers – product category
- Monitoring and optimization services
- Industrial energy management solutions
- Energy management systems
- Eastron SDM120 single-phase energy meter
- Eastron SDM630MCT CT-connected energy meter
- Eastron SDM630MCT-RC Rogowski coil energy meter
Energom Electronic Kft. is an official distributor of Eastron. Services across the Central and Eastern European region; product delivery across Europe. For SDM630 projects, Energom plans the metering points and the communication network, handles installation and commissioning, and integrates the meters with your monitoring platform or energy management system.
FAQ
What is the maximum current of the Eastron SDM630?
The SDM630 is a direct-connected three-phase meter rated up to 10(100) A for 3 × 230/400 V networks. The SDM630-M, -MB and -P cover 0.3–10(100) A; the SDM630-Modbus V2 covers 0.5–10(100) A.
What is the difference between the SDM630-M and the SDM630-Modbus V2?
The Eastron SDM630-M and SDM630-Modbus V2 are both direct-connected three-phase Modbus energy meters with RS485 Modbus RTU, rated up to 10(100) A. The SDM630-M covers 0.3–10(100) A, has Class B or C accuracy (EN 50470-3:2022) and operates from −40 to +70 °C; the SDM630-Modbus V2 covers 0.5–10(100) A, has Class 1 accuracy (IEC 62053-21) and in its standard version operates from −25 to +55 °C.
Can the Eastron SDM630 meter import and export separately?
The Eastron SDM630 range measures active power and energy bidirectionally and registers import and export separately; pulse output 1 can be set to total, import or export energy.