Key specifications at a glance

  • Connection: three-phase (3P4W, 3P3W) or single-phase (1P2W) network, Rogowski coil without an external integrator; range 0.5 / 1 / 5 / 10 kA (manufacturer coil recommendation: SDM630MCT-RC MID up to 10,000 A, SDM630MCT-RC up to 5,000 A); input 85 mV/kA (SDM630MCT-RC) or 100 mV/kA (SDM630MCT-RC MID); auxiliary supply input 100–277 V AC or 140–390 V DC
  • Accuracy class: SDM630MCT-RC: Class 1 (IEC 62053-21), Class B (EN 50470-3:2022); SDM630MCT-RC MID: Class 0.5S (IEC 62053-22), Class C (EN 50470-3:2022)
  • MID: SDM630MCT-RC MID version only; type examination certificate 0598/MID/B/26/036
  • Communication: RS485 Modbus RTU; 2 pulse outputs
  • Measured quantities: bidirectional kWh and kvarh; V, A, kW, var, VA, PF, Hz, max demand
  • Width: 72 mm

Applications

  • Metering of high-current main feeders in industrial equipment
  • PV systems
  • EV charging stations
  • Data centers
  • Dynamic load management (DLM / load balancing) solutions

Eastron SDM630MCT-RC models

The two versions need Rogowski coils of different sensitivity; the coil must match the meter.

Eastron SDM630MCT-RC models
Model Rating Distinguishing feature
SDM630MCT-RC three-phase, Rogowski 85 mV/kA, 0.5–10 kA Class 1 (IEC 62053-21), Class B, without MID
SDM630MCT-RC MID three-phase, Rogowski 100 mV/kA, 0.5–10 kA Class 0.5S (IEC 62053-22), Class C, MID-certified

Technical specifications – Rogowski coil Modbus energy meter

Technical specifications – Rogowski coil Modbus energy meter
Parameter Value
Current input Rogowski coil, no external integrator; 85 mV/kA (SDM630MCT-RC) or 100 mV/kA (SDM630MCT-RC MID)
Measuring range 0.5 / 1 / 5 / 10 kA
Nominal voltage 3 × 230/400 V AC
Voltage range 100–277 V AC (L-N), 100–480 V AC (L-L)
Frequency 50/60 Hz
Auxiliary supply 100–277 V AC or 140–390 V DC
Active energy accuracy SDM630MCT-RC: Class 1 (IEC 62053-21), Class B (EN 50470-3:2022); SDM630MCT-RC MID: Class 0.5S (IEC 62053-22), Class C (EN 50470-3:2022)
Reactive energy accuracy Class 2 (IEC 62053-23)
Accuracy of instantaneous values – SDM630MCT-RC MID voltage and current ±0.2%, frequency ±0.05%, power factor ±0.005, active and apparent power ±0.5%, reactive power ±1%
Accuracy of instantaneous values – SDM630MCT-RC voltage and current ±0.5%, frequency ±0.2%, power factor ±0.01, power values ±1% (5% Ib – Imax)
Overcurrent withstand 20 × Imax for 0.5 s
Power consumption voltage circuit ≤ 2 W / 10 VA; current circuit ≤ 0.05 VA
Insulation 4 kV AC for 1 minute; impulse 6 kV (1.2/50 µs)
Max reading 9,999,999.9 kWh or kvarh
Demand integration period max 60 minutes
RS485 Modbus RTU 2,400–38,400 bps (default 9,600); address 1–247; half duplex; floating-point data; max 1,000 m; response time < 30 ms
Pulse outputs output 2 fixed at 5,000 imp/kWh, 100 ms; output 1 configurable (total, import or export kWh or kvarh; 0.001–1,000 kWh or kvarh per pulse), pulse width 200, 100 or 60 ms
Recommended Rogowski coils – SDM630MCT-RC MID ESCT-RC60 (500 A, 50 mm window), ESCT-RC100 (1,000 A, 100 mm), ESCT-RC150 (5,000 A, 150 mm), ESCT-RC200 (10,000 A, 200 mm); class 0.2; with an output matching the meter's 100 mV/kA input (the ESCT-RC catalog lists these models with a standard 85 mV/kA output; the 100 mV/kA order version is confirmed with the quote)
Recommended Rogowski coils – SDM630MCT-RC ESCT-RC60, ESCT-RC100, ESCT-RC150 (500–5,000 A); class 0.5
Ingress protection IP51 front panel, IP20 whole meter (IEC 60529)
Operating temperature −40 to +70 °C
Storage temperature −40 to +80 °C
Relative humidity operating ≤ 90%, storage ≤ 95%, non-condensing
Vibration 10–150 Hz (IEC 60068-2-6)
Installation environment overvoltage and installation category CAT III; protective class II; mechanical environment M1; pollution degree 2; altitude max 2,000 m
Emissions CISPR 32 (radiated and conducted)
Dimensions (W × H × D) SDM630MCT-RC MID: 72 × 94.5 × 66 mm; SDM630MCT-RC: 72 × 94.5 × 65 mm; 35 mm DIN rail
Weight approx. 243 g
Wire size 0.5–1.5 mm², M3, 0.4 Nm
Compliance EN IEC 61326-1:2021, EN IEC 61326-2-3:2021, EN 61010-1:2010+A1:2019, EN 61010-2-030:2010, EN 50470-3:2022, EN IEC 62052-11:2021/A11:2022, IEC 62052-31:2015; SDM630MCT-RC MID: IEC 62053-22:2020; SDM630MCT-RC: IEC 62053-21:2020

Source: Eastron SDM630MCT-RC MID user manual (2026 V1.0, September 2026), SDM630MCT-RC user manual (V1.2, April 2026), manufacturer product page and load balancing application page (as of November 2026). Specifications are subject to change by the manufacturer.

How to choose

Billing-grade or internal monitoring

If the application requires certified metering, for example because energy is billed to a third party, choose the SDM630MCT-RC MID: it is MID-certified, with active energy accuracy of Class 0.5S (IEC 62053-22) and Class C (EN 50470-3:2022). For internal monitoring and submetering, the SDM630MCT-RC also works, with Class 1 (IEC 62053-21) and Class B accuracy.

Rogowski coil and measuring range

The meter is set to one of the 0.5, 1, 5 or 10 kA measuring ranges. The coil sensitivity must match the version: the SDM630MCT-RC takes 85 mV/kA, the SDM630MCT-RC MID takes 100 mV/kA. Eastron's coil list goes up to the ESCT-RC200 (10,000 A reference current, 200 mm window) for the SDM630MCT-RC MID and up to the ESCT-RC150 (5,000 A) for the SDM630MCT-RC. Eastron advises selecting the coil primarily by window size, that is, by conductor size.

Communication and system integration

The meter connects to a monitoring platform or an energy management system (EMS) over RS485 Modbus RTU, with a response time below 30 ms. It also has 2 pulse outputs; output 1 can be set to total, import or export energy.

Auxiliary supply

The auxiliary supply input accepts 100–277 V AC or 140–390 V DC; plan the meter supply as part of the panel design.

Lower-current feeders

For conventional current transformers with 1 A or 5 A secondary, use the Eastron SDM630MCT; for direct connection up to 100 A, use the SDM630.

Related services and products

Energom Electronic Kft. is an official distributor of Eastron. Services across the Central and Eastern European region; product delivery across Europe. For SDM630MCT-RC projects, Energom selects Rogowski coils that match the meter version, designs the metering chain, handles installation and commissioning, and integrates the meters with your monitoring platform or energy management system.

FAQ

Which SDM630MCT-RC version is MID-certified?

Only the SDM630MCT-RC MID, which works with 100 mV/kA Rogowski coils and has Class 0.5S active energy accuracy (IEC 62053-22). The SDM630MCT-RC with 85 mV/kA input is not MID-certified.

Which Rogowski coils work with the SDM630MCT-RC?

The coil sensitivity must match the meter: 85 mV/kA for the SDM630MCT-RC and 100 mV/kA for the SDM630MCT-RC MID. Eastron recommends the ESCT-RC60, ESCT-RC100, ESCT-RC150 and ESCT-RC200 (class 0.2) for the SDM630MCT-RC MID, and the ESCT-RC60, ESCT-RC100 and ESCT-RC150 (class 0.5) for the SDM630MCT-RC. The ESCT-RC catalog lists these coils with a standard 85 mV/kA output, so the 100 mV/kA order version needed for the MID meter is confirmed with the quote.

What current range does the SDM630MCT-RC cover?

The SDM630MCT-RC offers 0.5, 1, 5 and 10 kA measuring ranges with Rogowski coils that need no external integrator. Eastron's coil list goes up to the ESCT-RC200 (10,000 A reference current) for the SDM630MCT-RC MID and up to the ESCT-RC150 (5,000 A) for the SDM630MCT-RC.

Can the Eastron SDM630MCT-RC be used for dynamic load management (DLM)?

Eastron lists the SDM630MCT-RC MID (100 mV/kA) among its load balancing solutions. The meter passes measured values to the controlling system over RS485 Modbus RTU.

Request a quote

To help us prepare your quote, please include the number of metering points, the highest current of the main feeders, the busbar or cable size, the purpose of the metering, whether MID certification is needed (the MID version requires 100 mV/kA coils) and the receiving monitoring or energy management system.

Request a Quote

We respond within 24 hours on business days.

Request a Callback