Key specifications at a glance

  • Connection: SDM230-Lora: single-phase, direct, 0.15–10(100) A; SDM630MCT-Lora: three-phase, CT-connected, 1 A or 5 A secondary
  • Accuracy class: SDM230-Lora: Class 0.5 (IEC 62053-21), Class C (EN 50470-3:2022); SDM630MCT-Lora: Class 0.5S (IEC 62053-22), Class C (EN 50470-3:2022)
  • MID (MID version): SDM230-Lora: certificate T12800; SDM630MCT-Lora: 0598/MID/B/24/036 (0120/SGS0703)
  • Communication: LoRaWAN 1.0.2, Class C, OTAA or ABP, EU868; 2 pulse outputs; no RS485
  • Measured quantities: bidirectional kWh and kvarh; V, A, kW, var, VA, PF, Hz, max demand
  • Width: 2 DIN modules (36 mm, SDM230-Lora); 4 DIN modules (72 mm, SDM630MCT-Lora)

Applications

  • Sub-metering in residential buildings and residential complexes (SDM230-Lora)
  • Sub-metering in commercial buildings
  • Energy metering in industrial facilities
  • IoT-based energy management platforms and remote meter reading (SDM230-Lora)
  • Wireless metering of distributed equipment at renewable energy and infrastructure sites (SDM630MCT-Lora)

Eastron LoRaWAN energy meter models

Eastron also designates the SDM630MCT-Lora as SDM630MCT-LR and SDM630MCT-LoRaWAN-MID.

Eastron LoRaWAN energy meter models
Model Rating Key feature
SDM230-Lora single-phase, 230 V AC, 0.15–10(100) A, direct connection no current transformer needed, direct connection up to 100 A; 2 DIN modules
SDM630MCT-Lora 3 × 230/400 V AC, CT-connected, 1 A or 5 A secondary 1P2W, 3P3W and 3P4W networks; voltage and current THD measurement; 4 DIN modules

LoRaWAN energy meter technical specifications

LoRaWAN energy meter technical specifications
Parameter Value
Rated voltage SDM230-Lora: 230 V AC; SDM630MCT-Lora: 3 × 230/400 V AC
Voltage range SDM230-Lora: 100–277 V AC (L–N); SDM630MCT-Lora: 100–277 V AC (L–N), 100–480 V AC (L–L)
Frequency 50 or 60 Hz
Supply system SDM230-Lora: single-phase two-wire (1P2W); SDM630MCT-Lora: 1P2W, 3P3W or 3P4W, selectable (default 3P4W)
Current characteristics – SDM230-Lora Imin 0.15 A; Itr 1 A; starting current 0.04 A; Imax 100 A; overcurrent withstand 30 × Imax for 0.01 s
Current characteristics – SDM630MCT-Lora rated secondary current 5 A (1 A selectable); max 6 A; Imin 0.05 A; Itr 0.25 A; starting current 0.005 A; overcurrent withstand 20 × Imax for 0.5 s
CT and VT ratio – SDM630MCT-Lora CT primary 1–9999 A (secondary 1 A or 5 A); VT secondary 100–500 V, VT primary max 9999 V
Active energy accuracy SDM230-Lora: Class 0.5 (IEC 62053-21), Class C (EN 50470-3:2022); SDM630MCT-Lora: Class 0.5S (IEC 62053-22), Class C (EN 50470-3:2022)
Reactive energy accuracy Class 2 (IEC 62053-23)
Measurement accuracy voltage ±0.2%; current ±0.2%; frequency ±0.05%; power factor ±0.005 (SDM230-Lora), ±0.01 (SDM630MCT-Lora)
Total harmonic distortion – SDM630MCT-Lora voltage and current THD% per phase
Max demand configurable demand period, max 60 min; SDM230-Lora: off, 5, 10, 15, 30 or 60 min; SDM630MCT-Lora: 0, 5, 8, 10, 15, 20, 30 or 60 min
LoRaWAN LoRaWAN 1.0.2, Class C, OTAA or ABP, EU868 band; transmit power 13 dBm; data encoding based on Modbus ASCII, with CRC check
Auto-upload – SDM630MCT-Lora max 30 parameters; upload interval selectable in steps from 5 to 240 min, default 30 min
Pulse outputs – SDM230-Lora output 1 configurable: kWh or kvarh (total, import, export), 1, 10, 100 or 1000 imp/kWh, 60, 100 or 200 ms; output 2 fixed: import kWh, 1000 imp/kWh, 100 ms; passive, opto-coupled, 5–27 V DC, max 27 mA
Pulse outputs – SDM630MCT-Lora 1 fixed and 1 configurable; configurable output: kWh or kvarh, 0.01, 0.1, 1, 10, 100 or 1000 kWh/imp, 60, 100 or 200 ms
RS485 none
Power consumption voltage circuit ≤2 W / 10 VA; current circuit ≤3 VA (SDM230-Lora), ≤0.05 VA (SDM630MCT-Lora)
Insulation withstand 4 kV AC for 1 min; impulse voltage 6 kV (1.2/50 µs)
Safety classification installation and overvoltage category CAT III; protective class II; mechanical environment M1; pollution degree 2
Degree of protection (IEC 60529) IP51 front display, IP20 whole meter
Operating and storage temperature operating −40 to +70 °C; storage −40 to +80 °C
Humidity, altitude operating ≤90%, storage ≤95%, non-condensing; ≤2000 m
Dimensions (W × H × D), weight SDM230-Lora: 36 × 100 × 63 mm, approx. 162 g; SDM630MCT-Lora: 72 × 94.5 × 66 mm, approx. 253 g
Mounting, terminals 35 mm DIN rail; SDM230-Lora main terminals 4–35 mm², 3 Nm; SDM630MCT-Lora terminals 0.5–2.5 mm², 0.4 Nm
MID version both models: Directive 2014/32/EU (MID), per the EU declaration of conformity for the MID meter in the user manuals; notified body 0598
Standards EN IEC 61326-1:2021, EN IEC 61326-2-3:2021, EN 61010-1:2010+A1:2019, EN 61010-2-030:2010, EN 50470-3:2022, EN IEC 62052-11:2021/A11:2022, IEC 62052-31:2015; EMC tests: IEC 61000-4-2, -3, -4, -5, -6, -8, -11; emissions: CISPR 32

Source: Eastron SDM230-Lora user manual, 2026 V1.2 (April 2026), and Eastron SDM630MCT-LR user manual, V1.2 (September 2026). Specifications are subject to change by the manufacturer.

How to choose

Single-phase or three-phase circuit

For single-phase circuits up to 100 A, the SDM230-Lora connects directly, with no current transformer. For three-phase circuits, the SDM630MCT-Lora measures through current transformers: the secondary is 1 A or 5 A and the CT primary can be set from 1 to 9999 A, so the measurable current is set by the CT you select.

Supply system and measurement depth

The SDM630MCT-Lora works in 1P2W, 3P3W and 3P4W networks and measures voltage and current THD% on each phase. Where only single-phase consumption needs to be metered, the SDM230-Lora fits in 2 DIN modules.

MID-compliant billing

The user manuals of both models include an EU declaration of conformity under Directive 2014/32/EU (MID) for the MID meter, with active energy measured to Class C (EN 50470-3:2022). If the application requires certified metering, for example because energy is billed to a third party, specify the MID version when ordering; we confirm the version and order code with the quote. For internal cost allocation, the Class 0.5 or Class 0.5S accuracy is the guide.

LoRaWAN network and data upload

The meters communicate as LoRaWAN 1.0.2 Class C devices in the EU868 band and join the network via OTAA or ABP; receiving the data requires a LoRaWAN gateway and network server, either private or operator-run. The SDM630MCT-Lora uploads up to 30 parameters automatically; the interval is selectable in steps from 5 to 240 minutes, 30 minutes by default.

Local wired connection

There is no RS485 interface. For local wired transmission, use the two pulse outputs; on the SDM230-Lora, output 2 is fixed to import kWh at 1000 imp/kWh.

Related services and products

Energom Electronic Kft. is an official distributor of Eastron. Services across the Central and Eastern European region; product delivery across Europe. For Eastron LoRaWAN energy meters, Energom sizes the metering points and current transformers, installs and commissions the meters, and connects the metering data to your energy management or monitoring system.

FAQ

Do Eastron LoRaWAN energy meters have an RS485 Modbus output?

The Eastron LoRaWAN energy meters transmit data over LoRaWAN radio and provide two pulse outputs; they have no RS485 interface.

Which frequency band and LoRaWAN version do the Eastron LoRaWAN meters use?

In Europe, they operate in the EU868 band as LoRaWAN 1.0.2 Class C devices and join the network via OTAA or ABP. Transmit power is 13 dBm.

Are the SDM230-Lora and SDM630MCT-Lora MID certified?

MID certification of the Eastron SDM230-Lora and SDM630MCT-Lora applies to the MID version. The SDM230-Lora and SDM630MCT-Lora user manuals include an EU declaration of conformity under Directive 2014/32/EU (MID) for the MID meter, with active energy measured to Class C per EN 50470-3:2022.

How much current can the Eastron LoRaWAN energy meters measure?

The SDM230-Lora measures up to 100 A with direct connection. The SDM630MCT-Lora measures through current transformers with a 1 A or 5 A secondary; the CT primary can be set from 1 to 9999 A.

Do Eastron LoRaWAN meters need a LoRaWAN gateway?

Receiving data from Eastron LoRaWAN energy meters requires a LoRaWAN gateway and network server, either private or operator-run; the meters join the network via OTAA or ABP.