Key specifications at a glance

  • Technology: AGM VRLA, high rate
  • Nominal rating: 12 V; 103–710 W/cell (15 min, 1.67 V/cell, 25 °C); 24–200 Ah (C10, 1.80 V/cell, 25 °C)
  • Design life: Eurobat Long Life (10/12 years) for top-terminal models, Very Long Life (>12 years) for front-terminal models
  • Terminal: top or front design; M5, M6 or M8 thread, model dependent
  • Standards: IEC 60896-21 and -22
  • Container: flame-retardant ABS, UL94 V-0

Applications

  • UPS backup power – battery banks for short-duration, high-power discharge.
  • Data centers – as the battery bank of UPS systems; a main application per the FIAMM AGM engineering manual.
  • Telecom – a secondary application per the FIAMM AGM engineering manual.
  • Industry and utilities – a secondary application per the engineering manual.
  • Motion applications (FIAMM's Motion application category) – a secondary application per the engineering manual.

FLB models

FLB models
Model Nominal power (15 min, 1.67 V/cell, 25 °C) Capacity C10 (1.80 V/cell, 25 °C) Capacity C20 (1.75 V/cell, 25 °C) Weight (typical)
12FLB100P 103 W/cell 24 Ah 26 Ah 8.5 kg
12FLB150P 156 W/cell 44 Ah 48 Ah 14 kg
12FLB200P 204 W/cell 53 Ah 57 Ah 17 kg
12FLB250P 257 W/cell 75 Ah 80 Ah 24 kg
12FLB300P 311 W/cell 78 Ah 84 Ah 26 kg
12FLB350P 374 W/cell 90 Ah 95 Ah 30 kg
12FLB400P 415 W/cell 101 Ah 109 Ah 34 kg
12FLB450P 477 W/cell 115 Ah 124 Ah 38 kg
12FLB540P 540 W/cell 140 Ah 150 Ah 49 kg
12FLB700P 710 W/cell 200 Ah 216 Ah 61 kg

All models are 12 V blocks. Terminal design (top or front) and thread size depend on the model; specify the required design in your quote request.

Technical specifications – FLB VRLA AGM battery

Technical specifications – FLB VRLA AGM battery
Parameter Value
Nominal voltage 12 V
Electrolyte sulfuric acid, specific gravity 1.3 at 20 °C, absorbed in glass microfiber (AGM) separators
Dimensions (brochure column order: Length × Width × Height) 12FLB100P: 166 × 175 × 126 mm; 12FLB150P: 198 × 166 × 170 mm; 12FLB200P: 230 × 140 × 212 mm; 12FLB250P: 260 × 168 × 214 mm; 12FLB300P: 261 × 174 × 217 mm; 12FLB350P: 302 × 174 × 217 mm; 12FLB400P: 341 × 174 × 217 mm; 12FLB450P: 379 × 174 × 217 mm; 12FLB540P: 338 × 174 × 277 mm; 12FLB700P: 531 × 126 × 321 mm
Terminal torque M5: 5–6 Nm; M6: 7–9 Nm; M8: 10–12 Nm (by thread size)
Recommended float voltage 2.27 V/cell at 20 °C; temperature compensation: −2.5 mV/cell/°C (between −20 and +50 °C)
Typical float current approx. 0.6 mA/Ah (fully charged, 2.27 V/cell, 20 °C)
Boost (equalizing) charge 2.40 V/cell at 20 °C, max current limit 0.25 C10; stop at 0.001 C10 charging current or after 24 hours; recommended every 12 months
Recommended operating temperature 10–30 °C; operable from −20 to +50 °C, with reduced life expectancy above 20 °C
End-of-life criterion below 80% of nominal capacity
Gas recombination efficiency >98%
Safety valve opening pressure 0.15–0.30 atm (15–30 kPa)
Storage without refresh charge 9 months at 20 °C; 6 months at 30 °C; 3 months at 40 °C; refresh charge at the latest when the open-circuit voltage falls to 2.09 V/cell
Optimal storage conditions −10 to +30 °C, max 90% relative humidity
Parallel strings typically 4 (more depending on string voltage and cable length)
Remote venting system (RVS) optional accessory, top-side, for installation in enclosed cabinets (does not replace ventilation)
Maintenance no water topping-up required (VRLA); battery condition (voltage, temperature, internal resistance, valve) must still be checked periodically per the manufacturer's instructions
Transport non-hazardous per the manufacturer's classification; transportable by road, rail or air
Recyclability 99% recyclable at end of life
Standards IEC 60896-21, IEC 60896-22, IEC 62485-2, IEC 60695-11-10, BS 6290-4, BS 6290-1
Case material flammability rating V-0 (UL 94 material test; BS 6334)

Dimensions are listed in the brochure's Length × Width × Height column order; refer to the manufacturer's dimensional drawing for mounting orientation.

Source: FIAMM FLB brochure, Rev. 04.2026; FIAMM AGM (VRLA) engineering manual, edition 07/2026, Rev.16 (charging, temperature and storage data apply to the entire FIAMM AGM range). Specifications are subject to change by the manufacturer.

How to choose

Power over the discharge time

FLB sizing starts from the power per cell required for the UPS backup time. The model table gives 15-minute values to 1.67 V/cell, from 103 W/cell (12FLB100P) up to 710 W/cell (12FLB700P), so the range has a block size for both small and large UPS systems.

Capacity and its test condition

The brochure states FLB capacity under two conditions: C10 (1.80 V/cell) and C20 (1.75 V/cell), both at 25 °C. The same block shows a higher figure at C20 (for example, 12FLB400P: 101 Ah at C10, 109 Ah at C20), so always compare models using values measured under the same condition.

Terminal design and design life

Top-terminal models carry a Eurobat Long Life (10/12 years) classification and front-terminal models a Very Long Life (>12 years) classification. If the string requires front-access terminals, note this in your quote request.

Installation environment

Ventilation is mandatory in enclosed cabinets as well and must be sized per IEC 62485-2, which FIAMM lists as an applicable standard. An optional top-side remote venting system (RVS) is available as an add-on; it does not replace the sized ventilation, which is still required when an RVS is used. FIAMM recommends an operating temperature of 10–30 °C; above 20 °C, life expectancy is reduced.

How to choose
Situation Recommended model Why
Small UPS, limited space 12FLB100P–12FLB200P 103–204 W/cell, 8.5–17 kg
Mid-size UPS 12FLB250P–12FLB450P 257–477 W/cell
High-power UPS, fewer parallel strings 12FLB540P or 12FLB700P 540 or 710 W/cell

Related services and products

Energom Electronic Kft. is an official distributor of FIAMM. Energom sizes FLB battery banks to the UPS rating and backup time, handles installation and commissioning, and tracks battery condition through capacity testing. Services across the Central and Eastern European region; product delivery across Europe.

FAQ

What is the difference between the FLB C10 and C20 capacity ratings?

The FIAMM FLB C10 rating refers to a 10-hour discharge to 1.80 V/cell, the C20 rating to a 20-hour discharge to 1.75 V/cell, both at 25 °C. The longer discharge and lower end voltage give a higher C20 figure, for example 216 Ah instead of 200 Ah for the 12FLB700P.

What float voltage does the FIAMM FLB require?

For the FIAMM FLB, the FIAMM AGM engineering manual specifies a float voltage of 2.27 V/cell at 20 °C with −2.5 mV/cell/°C temperature compensation. When fully charged, the typical float current is approx. 0.6 mA/Ah.

How long can FLB batteries be stored without recharging?

Per the FIAMM AGM engineering manual, FIAMM FLB blocks can be stored without recharging for up to 9 months at 20 °C, 6 months at 30 °C and 3 months at 40 °C. A refresh charge is due at the latest when the open-circuit voltage falls to 2.09 V/cell.

What is the design life of the FLB?

Top-terminal FLB models carry a Eurobat Long Life (10/12 years) classification and front-terminal models a Very Long Life (>12 years) classification. FIAMM defines end of life as capacity below 80% of the nominal value; at operating temperatures above 20 °C, life expectancy is shorter. Design life is a design figure, not a guaranteed service life; actual service life depends on operating temperature, charger settings and discharge frequency.

Request a quote

For an accurate quote, include the UPS model and rating, the DC bus voltage, the required backup time and the preferred design (top or front terminals, open rack or enclosed cabinet).

Request a Quote

We respond within 24 hours on business days.

Request a Callback