Key specifications at a glance

  • Technology: OPzV: tubular plate, gel electrolyte VRLA
  • Nominal rating: 2 V; 220–3,640 Ah (C10, 1.80 V/cell, 20 °C)
  • Design life: 20 years; Eurobat Very Long Life (12 years and longer)
  • Terminal: M10 female
  • Standards: IEC 60896-21 and -22, DIN 40742, IEC 61427
  • Container: ABS; flame-retardant UL94 V-0 version on request

Design life is the manufacturer's design value, not a guaranteed service life: FIAMM recommends an operating temperature of 10–30 °C, and expected life decreases above 20 °C.

Applications

  • Telecom: backup power for DC telecom power plants.
  • Industry and utilities: DC auxiliary and backup power.
  • Applications requiring high operational reliability, including intensive cyclic use.

FIAMM SMG models

All models are 2 V cells; capacity is rated at C10 discharge to 1.80 V/cell at 20 °C. Dimensions follow the column order of the manufacturer's brochure: length × width × height.

FIAMM SMG models
Model Nominal capacity DIN 40742 reference Dimensions (mm) Typical weight
SMG 220 220 Ah 4 OPzV 200 103 × 206 × 407 19.0 kg
SMG 275 275 Ah 5 OPzV 250 124 × 206 × 407 23.0 kg
SMG 330 330 Ah 6 OPzV 300 145 × 206 × 407 26.6 kg
SMG 380 380 Ah 5 OPzV 350 124 × 206 × 523 30.0 kg
SMG 460 460 Ah 6 OPzV 420 145 × 206 × 523 33.3 kg
SMG 530 530 Ah 7 OPzV 490 166 × 206 × 523 39.0 kg
SMG 720 720 Ah 6 OPzV 600 145 × 206 × 698 48.5 kg
SMG 960 960 Ah 8 OPzV 800 210 × 191 × 700 64.6 kg
SMG 1200 1,200 Ah 10 OPzV 1000 210 × 233 × 700 80.4 kg
SMG 1440 1,440 Ah 12 OPzV 1200 210 × 275 × 700 95.1 kg
SMG 1680 1,680 Ah 12 OPzV 1500 210 × 275 × 849 112 kg
SMG 2005 2,000 Ah 14 OPzV 1750 212 × 399 × 826 135 kg
SMG 2250 2,250 Ah 16 OPzV 2000 212 × 399 × 826 151 kg
SMG 2520 2,520 Ah 18 OPzV 2250 212 × 487 × 826 171 kg
SMG 2800 2,800 Ah 20 OPzV 2500 212 × 487 × 826 189 kg
SMG 3080 3,080 Ah 22 OPzV 2750 212 × 576 × 826 208 kg
SMG 3350 3,350 Ah 24 OPzV 3000 212 × 576 × 826 226 kg
SMG 3640 3,640 Ah 26 OPzV 3250 212 × 576 × 826 240 kg

Per the manufacturer's model table, the SMG 2005 has a nominal capacity of 2,000 Ah.

OPzV battery specifications

OPzV battery specifications
Parameter Value
Cell voltage 2 V
Technology VRLA, gel electrolyte (OPzV)
Positive plate tubular, die-cast positive grid
Separator high-porosity microporous PVC separator
Terminal M10 female; tightening torque 20–25 Nm
Safety valve opening pressure 0.15–0.30 atm (15–30 kPa)
Installation position vertical or horizontal; FIAMM suggests limiting horizontal installation to cells up to approx. 1,700 Ah
Recommended float voltage 2.25 V/cell at 20 °C
Temperature compensation −2.5 mV/cell/°C, between −20 and +50 °C
Typical float current approx. 0.6 mA/Ah (fully charged cell, 2.25 V/cell, 20 °C)
Periodic boost charge 2.40 V/cell at 20 °C, with current limited to max 0.25 C10; stop at 0.001 C10 charge current or after 24 hours; recommended every 12 months
Recommended operating temperature 10–30 °C; operable between −20 and +50 °C, with reduced expected life above 20 °C
End-of-life criterion capacity falls below 80% of nominal
Self-discharge low; suitable for storage and off-float operation
Storage time without recharge 9 months at 20 °C; 6 months at 30 °C; 3 months at 40 °C
Recommended storage temperature between −10 and +30 °C
Container ABS; flame-retardant UL94 V-0 version on request
Standards (brochure) IEC 60896-21 and -22, DIN 40742, IEC 61427, DIN 43539 T5
Applicable standards (engineering manual) IEC 60896-21, IEC 60896-22, EN 62485-2, BS 6290-1; IEC 60695-11-10 (flame-retardant container version)
Recyclability all components recyclable at end of life

Source: FIAMM SMG product brochure, Rev. 11.2025; FIAMM GEL engineering manual, Edition 07/2026, Rev.15. Specifications are subject to change by the manufacturer.

How to choose

  • Capacity and backup time: the 18 models cover a C10 capacity range from 220 Ah to 3,640 Ah. The right model is sized from the load current, the required backup time and the allowable end-of-discharge voltage.
  • Footprint and floor loading: cell height ranges from 407 mm to 849 mm and weight from 19.0 kg to 240 kg. The SMG 2005 and all larger models share an 826 mm height, so rack or cabinet design should start from the dimensions in the model table.
  • Horizontal installation: cells can also be installed horizontally in racks; the manufacturer's manual suggests limiting this to cells up to approx. 1,700 Ah, which covers the models up to the SMG 1680.
  • Charger and temperature: the rectifier must be set to a float voltage of 2.25 V/cell (20 °C) with −2.5 mV/cell/°C temperature compensation. FIAMM recommends an operating temperature of 10–30 °C; battery life is best at around 20 °C and decreases above it.
  • Container version: the standard container is ABS; a flame-retardant UL94 V-0 container is available on request only; whether it is needed depends on the project's fire protection requirements.

Related services and products

Energom Electronic Kft. is an official distributor of FIAMM. Energom sizes SMG battery banks, matches the cell count to the rectifier settings, and handles installation, commissioning and periodic maintenance. Services across the Central and Eastern European region; product delivery across Europe.

FAQ

Can FIAMM SMG OPzV batteries be installed horizontally?

Yes. FIAMM SMG cells can be installed vertically or horizontally; FIAMM suggests limiting horizontal installation to cells up to approx. 1,700 Ah, which covers the SMG 220 to SMG 1680 models.

What float voltage do SMG OPzV cells need?

For FIAMM SMG cells, FIAMM recommends a float voltage of 2.25 V/cell at 20 °C, with −2.5 mV/cell/°C temperature compensation between −20 and +50 °C. A fully charged cell draws a typical float current of approx. 0.6 mA/Ah.

How long can SMG cells be stored without recharging?

According to the manufacturer's manual, FIAMM SMG cells can be stored without recharging for 9 months at 20 °C, 6 months at 30 °C and 3 months at 40 °C. The recommended storage temperature is between −10 and +30 °C.

How does an SMG (OPzV) cell differ from an OPzS cell?

The SMG is a valve-regulated (VRLA) cell with gel electrolyte: no water topping-up is required, and the cell is never topped up with water; its condition (voltage, temperature, internal resistance, valve) must still be checked periodically. An OPzS cell is a vented design with liquid electrolyte that needs periodic water top-ups; FIAMM's range of this type is the LM.

Which FIAMM SMG model corresponds to a 6 OPzV 600 cell?

Per the manufacturer's model table, the SMG 720 corresponds to the DIN 40742 designation 6 OPzV 600, with a nominal capacity of 720 Ah (C10, 1.80 V/cell, 20 °C). The DIN designations of all other models are listed in the model table.

Request a quote

When requesting a quote, include the nominal DC system voltage, the load current, the required backup time, the orientation (vertical or horizontal) and the room's operating temperature.

Request a Quote

We respond within 24 hours on business days.

Request a Callback