Eastron DCM230 5–1000 V DIN Rail DC Energy Meter
The Eastron DCM230 is a DIN rail DC energy meter family (DCM230-1, DCM230-2) for DC system metering through an external shunt. The datasheet lists 5–300, 5–600 and 5–1000 V DC at family level, without assigning them to a model; the DCM230-2-150 … -800 models are rated 100–1000 V DC and 150–800 A. It offers bidirectional metering, Class 1 accuracy (IEC 62053-41), RS485 Modbus RTU and a 2-module (36 mm) width.
Key specifications at a glance
- Measurement voltage: 5–300, 5–600 or 5–1000 V DC (datasheet, family level, not assigned to a model); DCM230-2-150 … -800: 100–1000 V DC
- Current input: external shunt, 75 mV (60 or 45 mV optional); DCM230-2-150 … -800: 150–800 A rated
- Accuracy class: Class 1 (IEC 62053-41 / GB/T 33708-2017)
- Communication: RS485 Modbus RTU + 1 pulse output
- Measured quantities: bidirectional (import and export kWh); W, V, A
- Width: 2 DIN modules (36 mm)
Applications
- Energy metering and monitoring in DC systems
- DC-side metering in EV chargers (DCM230-2)
- Separate import and export energy measurement in bidirectional DC circuits
- Sending DC metering data to monitoring or energy management systems over RS485 Modbus RTU
Eastron DCM230 DC energy meter models
The DCM230-1 runs from an AC auxiliary supply and the DCM230-2 from a DC auxiliary supply; the last number in a DCM230-2 model code is the rated shunt current.
| Model | Rating | Key feature |
|---|---|---|
| DCM230-1 | input voltage depends on the order version (see Voltage level); external shunt 75, 60 or 45 mV | auxiliary supply 85–276 V AC |
| DCM230-2-150 | 100–1000 V DC; 150 A / 75 mV shunt | measuring range 7.5–150 (180) A; auxiliary supply 9–40 V DC |
| DCM230-2-200 | 100–1000 V DC; 200 A / 75 mV shunt | measuring range 10–200 (240) A; auxiliary supply 9–40 V DC |
| DCM230-2-300 | 100–1000 V DC; 300 A / 75 mV shunt | measuring range 15–300 (360) A; auxiliary supply 9–40 V DC |
| DCM230-2-400 | 100–1000 V DC; 400 A / 75 mV shunt | measuring range 20–400 (480) A; auxiliary supply 9–40 V DC |
| DCM230-2-600 | 100–1000 V DC; 600 A / 75 mV shunt | measuring range 30–600 (720) A; auxiliary supply 9–40 V DC |
| DCM230-2-800 | 100–1000 V DC; 800 A / 75 mV shunt | measuring range 40–800 (960) A; auxiliary supply 9–40 V DC |
DC energy meter technical specifications
| Parameter | Value |
|---|---|
| Measurement voltage | 5–300, 5–600 or 5–1000 V DC (version dependent); DCM230-2-150 … -800: 100–1000 V DC |
| Current input | external shunt; secondary 75 mV (default), 60 or 45 mV optional; shunt primary current configurable from 1 to 2000 A |
| Current range – DCM230-2 | by model, from 7.5–150 (180) A to 40–800 (960) A (see model table) |
| Shunt connection | in the positive or negative line, selectable (default: negative) |
| Auxiliary power supply | DCM230-1: 85–276 V AC, ≤1 W / 5 VA; DCM230-2: 9–40 V DC, ≤1 W |
| Accuracy class | Class 1 (IEC 62053-41 / GB/T 33708-2017) |
| Measurement accuracy | voltage 0.5%; current 0.5%; power 1%; active energy 1% |
| Power consumption (measuring circuits) | voltage input ≤0.5 VA; current input ≤0.1 VA |
| Measured quantities | bidirectional (import and export kWh); W, V, A |
| Display | backlit LCD; DCM230-2: max reading 999,999.9999 kWh, resettable partial energy register |
| RS485 Modbus RTU | half-duplex; 1200–19,200 bps; address 1–247; parity even, odd or none; 1 or 2 stop bits; max 64 devices per bus; max 1000 m; response time ≤100 ms |
| Pulse output | 1, 10, 100 or 1000 imp/kWh; pulse width 60, 100 or 200 ms; total, import or export kWh; passive, IEC 62053-31 Class A |
| Overcurrent alarm – DCM230-2 | alarm when current exceeds the configured shunt primary value; indicated by LED and Modbus register |
| Insulation withstand – DCM230-2 | 4.4 kV AC for 1 min; impulse voltage 6.4 kV (1.2/50 µs) |
| Installation category – DCM230-2 | CAT III |
| Environmental classification | mechanical environment M1, electromagnetic environment E2; pollution degree 2; max 2000 m; protective class II |
| Operating temperature – DCM230-2 | −30 to +60 °C |
| Storage temperature, humidity | storage −40 to +70 °C; operating humidity ≤90%, storage ≤95%, non-condensing |
| Degree of protection | IP51 (indoor) |
| EMC immunity | electrostatic discharge 8 kV contact, 15 kV air; fast transients and surge 4 kV (AC auxiliary supply); radiated RF fields per IEC 61000-4-3 |
| Standards | EMC: EN 61326-1:2013 and EN 61326-2-3:2013; Low Voltage Directive: EN 61010-1:2010+A1:2019 and EN 61010-2-030:2010; metering: IEC 62053-41 / GB/T 33708-2017 |
| Dimensions (W × H × D), weight | 36 × 100 × 63 mm (DIN 43880); DCM230-2: 220 g |
| Terminals | screw terminals; auxiliary, RS485 and pulse 0.5–1.5 mm²; DC± and I± 0.5–2.5 mm² (DCM230-2); 0.2 Nm |
Source: Eastron DCM230 series datasheet (August 2024) and Eastron DCM230-2 user manual, V2.1 (March 2026); the EV charger application is from the manufacturer's DCM230-2-400 product page. Specifications are subject to change by the manufacturer.
How to choose
Auxiliary supply: AC or DC
Where an AC auxiliary supply is available at the metering point, choose the DCM230-1 (85–276 V AC). Where only a 9–40 V DC auxiliary supply is available, choose the DCM230-2.
Voltage level
The DCM230 datasheet lists 5–300, 5–600 and 5–1000 V DC input ranges without assigning them to a model; choose the version that covers the highest DC voltage in the system and confirm it when ordering. The DCM230-2-150 … -800 models measure 100–1000 V DC.
Current and shunt
The DCM230 measures current through an external shunt. The DCM230-2 model code gives the rated shunt current (150–800 A); the shunt primary current is configurable on the meter from 1 to 2000 A, and the secondary signal is 75 mV (60 or 45 mV optional). Size the shunt for the highest operating current.
Communication and data collection
Up to 64 devices can share one RS485 Modbus RTU bus, with a bus length of up to 1000 m, so multiple DC metering points can feed a single monitoring or energy management system. The pulse output suits a simple counter input.
Billing-grade metering
The DCM230 is a Class 1 meter per IEC 62053-41, intended for internal metering, monitoring and cost allocation. If the application requires certified metering, we review the applicable compliance requirements for the selected model at the quotation stage. For billing-grade metering in DC fast chargers, Eastron offers the DCM6 series.
Installation environment
The meter is rated IP51 for indoor use and is 2 DIN modules (36 mm) wide; the DCM230-2 operates from −30 to +60 °C.
Related services and products
- Energy meters and current transformers – product category
- Energy monitoring and optimization – service
- Industrial energy management – solution
- EV charging infrastructure solutions
- EV chargers – product category
- Eastron DCM6 DC energy meter
Energom Electronic Kft. is an official distributor of Eastron. Services across the Central and Eastern European region; product delivery across Europe. For Eastron DCM230 meters, Energom sizes the shunt and selects the meter version, installs and commissions the meters, and connects the Modbus data to your monitoring or energy management system.
FAQ
What is the difference between the DCM230-1 and the DCM230-2?
The DCM230-1 runs from an 85–276 V AC auxiliary supply. The DCM230-2 uses a 9–40 V DC auxiliary supply, measures 100–1000 V DC and is available in models matched to 150–800 A rated shunts (DCM230-2-150 … -800).
Does the Eastron DCM230 need a separate shunt?
The DCM230 measures current through an external shunt; the shunt secondary signal is 75 mV (60 or 45 mV optional), and the shunt primary current is configurable on the meter from 1 to 2000 A. The shunt can be connected in the positive or the negative line.
Does the Eastron DCM230 support Modbus RTU?
The DCM230 has an RS485 Modbus RTU interface (1200–19,200 bps, max 64 devices, max 1000 m) and one pulse output.
Does the DCM230 measure bidirectional energy flow?
The DCM230 measures import and export kWh separately, along with power, voltage and current.
Can the Eastron DCM230 be used for billing?
The DCM230 is a Class 1 meter per IEC 62053-41 for internal metering, monitoring and cost allocation. If the application requires certified metering, we review the applicable compliance requirements for the selected model at the quotation stage; for DC fast chargers, Eastron offers the DCM6 series.
Request a quote
For your quote, please include the purpose of the metering (internal metering, monitoring or billing), the DC system voltage, the maximum operating current, the available auxiliary supply (AC or DC), the number of metering points and the receiving monitoring system.
We respond within 24 hours on business days.