Riello UPS Sentinel Dual (SDU) 4–10 kVA Single-Phase Output Online UPS
The Riello UPS Sentinel Dual (SDU) is a 4–10 kVA online (double-conversion) UPS range with single-phase output, VFI-SS-111 classification and input THDi of ≤2%. Built in rack or tower format with hot-swappable internal batteries (except ER models), the Sentinel Dual serves server rooms, network, security and electro-medical equipment; the 8 kVA and 10 kVA TM models also accept a three-phase input.
Key specifications at a glance
- Output power factor: 1.0 (kW = kVA) for SDU 5000–10000; SDU 4000: 0.9 (4,000 VA / 3,600 W)
- Topology: online, double-conversion; VFI-SS-111 (IEC 62040-3)
- Efficiency (online mode): max 95%
- Efficiency (ECO mode): max 98%
- Input THDi: ≤2%
- Parallel capability: max 3 units, capacity or N+1 redundant, with optional parallel card (SDU 4000 cannot be paralleled)
Applications
- Mission-critical applications
- IT, network and server rack applications
- Electro-medical devices
- Security systems
- Emergency systems: emergency lighting, fire detection and extinguishing systems, alarms
Sentinel Dual models
| Model | Rated power | Distinguishing feature |
|---|---|---|
| SDU 4000 | 4,000 VA / 3,600 W | smallest model, cannot be paralleled |
| SDU 5000, SDU 5000 PDIST | 5,000 VA / 5,000 W | single-enclosure unit; PDIST: extended IEC socket set |
| SDU 6000, SDU 6000 PDIST | 6,000 VA / 6,000 W | single-enclosure unit; PDIST: extended IEC socket set |
| SDU 6000 ER | 6,000 VA / 6,000 W | no internal batteries, more powerful charger |
| SDU 8000 | 8,000 VA / 8,000 W | UPS and battery enclosure (2 units) |
| SDU 10000 | 10,000 VA / 10,000 W | UPS and battery enclosure (2 units) |
| SDU 10000 DI | 10,000 VA / 10,000 W | dual input (separate bypass input) |
| SDU 10000 DI ER | 10,000 VA / 10,000 W | dual input, no internal batteries, more powerful charger |
| SDU 8000 TM | 8,000 VA / 8,000 W | three-phase input, single-phase output (3:1) |
| SDU 10000 TM | 10,000 VA / 10,000 W | three-phase input, single-phase output (3:1) |
UPS technical specifications
| Parameter | Value |
|---|---|
| Input rated voltage | 220 / 230 / 240 V single-phase; TM models: 380 / 400 / 415 V three-phase (3W+N+PE) or 220 / 230 / 240 V single-phase (1W+N+PE) |
| Input voltage tolerance | 230 V ±20%; TM models: 400 V ±20% (three-phase), 230 V ±20% (single-phase) |
| Minimum input voltage | 184 V; TM models: 318 V with three-phase input, 184 V with single-phase input |
| Input frequency | 50 / 60 Hz |
| Input power factor | >0.98 |
| Bypass voltage tolerance | 180–264 V (selectable in ECO or SMART ACTIVE mode) |
| Bypass frequency tolerance | selected frequency ±5% (user-selectable) |
| Bypass overload | below 110%: continuous; 130%: 1 h; 150%: 10 min; above 150%: 3 s |
| Inverter overload | 150% (also during mains failure); duration not stated by the manufacturer |
| Output voltage | 220 / 230 / 240 V, selectable |
| Output frequency | 50 / 60 Hz, selectable; frequency-converter operation available |
| Output voltage distortion | <1% with linear load; <3% with non-linear load |
| Output voltage regulation | static: 1.5%; dynamic: ≤5% within 20 ms |
| Crest factor | 3:1 |
| Operation without battery use | batteries do not cut in for mains failures shorter than 20 ms or with single-phase input between 184 V and 276 V (230 V ±20%); the manufacturer does not state such a window for the three-phase input of the TM models |
| Operating modes | ON LINE, ECO, SMART ACTIVE, STANDBY OFF (emergency only), frequency converter |
| Battery | internal VRLA AGM lead-acid (no water topping-up required), hot-swappable; ER models have no internal batteries |
| Recharge time | 4–6 h |
| Battery expansion | external BTC SDU battery cabinets, 96 V, 180 V and 240 V versions |
| Communications | USB, RS232, communications slot, R.E.P.O. and input contact |
| Connections | input: terminal board; output: terminal board + 2× C13 + 1× C19 (SDU 4000); terminal board + 2× C19 (SDU 5000, 6000); terminal board + 8× C13 + 2× C19 (PDIST); terminal board + 2× C13 + 3× C19 (SDU 8000 and 10000 variants) |
| Dimensions (W × D × H) | single enclosure: 131 × 640 × 448 mm (tower) or 19-inch × 640 mm × 3U (rack) – SDU 4000, 5000, 6000 and ER models; SDU 8000 and 10000 (DI, TM): 2 enclosures of the same size |
| Net weight | 38 kg (SDU 4000); 45 kg (SDU 5000); 46 kg (SDU 6000); 20 kg (SDU 6000 ER); 19 + 53 kg (SDU 8000, 8000 TM); 20 + 62 kg (SDU 10000, 10000 DI, 10000 TM); 21 kg (SDU 10000 DI ER) |
| Operating temperature | 0–40 °C (recommended for battery life: 20–25 °C) |
| Relative humidity | 5–95%, non-condensing |
| Noise level | <48 dBA at 1 m, ECO mode |
| Standards and directives | VFI-SS-111 (IEC 62040-3); safety: IEC EN 62040-1; EMC: IEC EN 62040-2; 2014/35/EU (LVD), 2014/30/EU (EMC); RoHS compliant |
| Color | RAL 9005 |
Source: Riello UPS catalog sheet (DATSDUA1Y23BREN, April 2023) and Riello UPS product page model tables (November 2026). Specifications are subject to change by the manufacturer.
How to choose
Power requirement and power factor
SDU 5000–10000 models have a 1.0 output power factor, so the kVA rating is also available in kW. The SDU 4000 has a 0.9 power factor: 3,600 W of real power at 4,000 VA.
Input supply: single-phase, three-phase or dual input
The base models fit a single-phase supply. Where a three-phase supply is available, the SDU 8000 TM and SDU 10000 TM deliver single-phase output from a 380 / 400 / 415 V three-phase input. Where a separate bypass feed is planned, choose the dual-input SDU 10000 DI or SDU 10000 DI ER.
Runtime
Runtime on the internal-battery models can be extended with external BTC SDU battery cabinets. For long runtimes, the ER models (SDU 6000 ER, SDU 10000 DI ER) have no internal batteries and a more powerful charger; the external battery bank then sets the runtime.
Redundancy
SDU 5000–10000 models can run up to 3 units in parallel with the optional parallel card, for added capacity or N+1 redundancy. The SDU 4000 cannot be paralleled, so redundant designs start at 5,000 VA.
Output connections and footprint
Every model offers a terminal-board output. For many IEC-plug loads, the SDU 5000 PDIST and SDU 6000 PDIST add 8× C13 + 2× C19 sockets. SDU 4000, 5000, 6000 and the ER models come in a single enclosure (3U rack); SDU 8000 and 10000 models use two enclosures, one for the UPS and one for the batteries.
Related services and products
- UPS maintenance and inspection
- Uninterruptible power supply solutions
- UPS systems – product category
- Industrial batteries – product category
- Riello UPS Sentinel Dual2 (SD2) 1–3 kVA
Energom Electronic Kft. is an official distributor of Riello UPS. Energom sizes Sentinel Dual systems to the load, the available supply and the required runtime, then handles installation, commissioning and scheduled maintenance. Services across the Central and Eastern European region; product delivery across Europe.
FAQ
Can the Sentinel Dual UPS be paralleled?
Yes. The Riello UPS Sentinel Dual SDU 5000–10000 models can run up to 3 units in parallel with an optional parallel card, for capacity or N+1 redundancy. The SDU 4000 cannot be paralleled.
Can the Sentinel Dual connect to a three-phase supply?
Yes, with the Sentinel Dual TM models: the SDU 8000 TM and SDU 10000 TM accept a 380 / 400 / 415 V three-phase or 220 / 230 / 240 V single-phase input and deliver a 220 / 230 / 240 V single-phase output.
How can the Sentinel Dual runtime be extended?
The Sentinel Dual runtime is extended with external BTC SDU battery cabinets, available in 96 V, 180 V and 240 V versions. For long runtimes, the SDU 6000 ER and SDU 10000 DI ER run without internal batteries and with a more powerful charger.
What operating modes does the Sentinel Dual support?
The Sentinel Dual supports ON LINE (double conversion), ECO, SMART ACTIVE (automatic mode selection based on mains quality), STANDBY OFF (emergency-only operation during mains failure) and frequency converter. Efficiency is up to 95% in online mode and up to 98% in ECO mode.
Request a quote
For a quote, share the protected load (kVA and kW), the available supply (single-phase, three-phase or dual input), the required runtime, the redundancy requirement and the installation format.
We respond within 24 hours on business days.