Solis S6-EH3P(30-60)K-H(21A) 30–60 kW Three-Phase Hybrid Inverter
The Solis S6-EH3P(30-60)K-H(21A) is a 30–60 kW three-phase hybrid inverter range for commercial PV storage with high-voltage (150–800 V) Li-ion batteries. It has three or four MPPTs, two battery ports, generator input, 97.7% max and 97.3% European efficiency, and backup switchover under 10 ms (20 ms in parallel). Same-model units can be paralleled: six without a Solis STS cabinet, up to 600 kW with one, each with its own battery.
Key specifications at a glance
- Rated AC power: 30 / 40 / 50 / 60 kW; max 30–60 kVA; 3/N/PE, 230/400 V
- DC input: max 1000 V; MPPT 150–850 V; 3 MPPTs / 6 strings (30 kW), 4 MPPTs / 8 strings (40–60 kW); 42 A per MPPT, 21 A per string
- Efficiency: max 97.7%; European 97.3%
- Battery: Li-ion, 150–800 V; 2 battery ports; max 80 A per port (30–50 kW), 84 A (60 kW)
- Backup operation: rated 30–60 kW; 1.6 × rated power for 2 s, 1.5 × for 10 s; switchover <10 ms (<20 ms in parallel systems)
- Compliance, protection rating: EN 50549-1 / EN 50549-10 (TÜV Rheinland certificate); EN 62109-1/-2; IP66
Applications
- Solar-plus-storage systems for commercial facilities, in on-grid and off-grid operation.
- Sites with unstable or weak grids and generator-hybrid systems.
- Integration of solar, wind and diesel generator sources through one inverter.
- DC- and AC-coupled retrofits and system expansion.
- Demand management, export prevention (anti-backflow), dynamic tariff optimization and virtual power plant (VPP) compatibility.
- Dynamic reactive power compensation to improve the grid power factor.
Solis S6-EH3P hybrid inverter models
| Model | Rated power | Key differentiator |
|---|---|---|
| S6-EH3P30K-H(21A) | 30 kW | 3 MPPTs / 6 strings; max 80 A and 33 kW per battery port |
| S6-EH3P40K-H(21A) | 40 kW | 4 MPPTs / 8 strings; recommended max PV 80 kW |
| S6-EH3P50K-H(21A) | 50 kW | 4 MPPTs / 8 strings; recommended max PV 100 kW |
| S6-EH3P60K-H(21A) | 60 kW | 4 MPPTs / 8 strings; max 84 A per battery port; recommended max PV 100 kW |
Solis S6-EH3P hybrid inverter specifications
| Parameter | Value |
|---|---|
| Rated AC power | 30 / 40 / 50 / 60 kW; max 30 / 40 / 50 / 60 kVA |
| Rated grid output current | 45.6 / 60.8 / 76 / 91.2 A (220/380 V); 43.3 / 57.7 / 72.2 / 86.6 A (230/400 V) |
| Power factor, current distortion | > 0.99 (0.8 leading … 0.8 lagging); THDi < 3% |
| AC input from grid | max 60 / 80 / 100 kW (30 / 40 / 50 kW model); voltage range 304–460 V |
| Max DC input voltage | 1000 V |
| Rated and start-up DC voltage | rated 600 V; start-up 180 V |
| MPPT voltage range | 150–850 V |
| MPPTs / strings | 3 / 6 (30 kW); 4 / 8 (40–60 kW) |
| Max input current | 42 A per MPPT; 21 A per string |
| Max short-circuit current per MPPT | 60 A |
| Recommended and max usable PV power | 60 / 80 / 100 / 100 kW (30 / 40 / 50 / 60 kW model) |
| Battery | Li-ion, 150–800 V; 100–314 Ah battery modules; 2 battery ports, 2 BMS ports; CAN |
| Max charge and discharge current | 80 A per port (30–50 kW), 84 A per port (60 kW) |
| Charge and discharge power per port | 33 kW (30 kW model); 35 kW (40–60 kW models) |
| Backup output | rated 30–60 kW; 1.6 × rated power for 2 s, 1.5 × for 10 s; 3/N/PE, 220/380 V or 230/400 V; 50/60 Hz; THDv < 2% at linear load |
| Switchover time | < 10 ms (single inverter); < 20 ms (parallel system) |
| Max AC passthrough current | 91.2 / 121.6 / 152.0 / 152.0 A (30 / 40 / 50 / 60 kW model, 220/380 V); 86.6 / 115.4 / 144.4 / 152.0 A (230/400 V) |
| Generator input | max 30 / 40 / 50 / 60 kW; 3/N/PE, 220/380 V or 230/400 V; 50/60 Hz |
| Max efficiency | 97.7% |
| European efficiency | 97.3% |
| Battery charging efficiency | max 98.5% from PV; max 97.8% from AC |
| Battery discharge efficiency | 97.5% |
| Protections | Type II DC / Type II AC surge protection; output overcurrent protection; insulation resistance monitoring; residual current detection; integrated PV switch; DC reverse polarity protection; AFCI 2.0 optional |
| Protection class, overvoltage category | class I; PV II, battery II, AC III |
| Protection rating | IP66 |
| Dimensions (W × H × D), weight | 530 × 880 × 290 mm; 76 kg |
| Self-consumption | < 35 W |
| Operating temperature, humidity, altitude | −25 to +60 °C; 0–100% relative humidity; max 4000 m |
| Cooling, topology | intelligent redundant fan cooling; non-isolated (transformerless) |
| Display | 7-inch LCD, Bluetooth, app |
| Communication interfaces | standard: Wi-Fi, LAN, Bluetooth, 2 × CAN-BMS, 2 × CAN-parallel, RS485 meter, RS485, DRM, 3 × DI, 3 × DO; optional 4G |
| Connections | PV: MC4; battery: terminal connectors; AC: OT terminal |
| Parallel system | max 6 units of the same model without a Solis STS cabinet; 7–10 units (up to 600 kW) require a Solis STS cabinet; each inverter needs its own battery |
| Grid compliance | EN 50549-1 / EN 50549-10 (TÜV Rheinland certificate) |
| Safety, EMC | EN 62109-1/-2; IEC/EN 61000-6-2/-4; EN 55011 |
Source: Solis S6-EH3P(30-60)K-H(21A) Hungarian-language datasheet, V1.8; Solis S6-EH3P(30-60)K-H(21A) user manual (EUR), V1.2 (2026-11; source of the max AC passthrough current); Solis Hungarian product page, November 2026. Specifications are subject to change by the manufacturer.
How to choose
Power rating and PV array
| Situation | Suggested model | Why |
|---|---|---|
| PV array up to 60 kW, three MPPTs sufficient | S6-EH3P30K-H(21A) | 3 MPPTs / 6 strings, recommended max PV 60 kW |
| PV array up to 80 kW | S6-EH3P40K-H(21A) | 4 MPPTs / 8 strings, recommended max PV 80 kW |
| PV array up to 100 kW | S6-EH3P50K-H(21A) or S6-EH3P60K-H(21A) | 4 MPPTs / 8 strings, recommended max PV 100 kW |
| Inverter capacity above 60 kW | several units of the same model in parallel | max 6 units without STS; 7–10 units with a Solis STS cabinet, up to 600 kW |
Battery
- The two independent battery ports accept 150–800 V Li-ion batteries with CAN-based BMS communication; per the datasheet, the inverter is compatible with 100–314 Ah battery modules.
- Max charge and discharge current per port is 80 A (30–50 kW) or 84 A (60 kW), and charge and discharge power per port is 33 kW (30 kW model) or 35 kW (40–60 kW models).
Backup operation and generator
- In backup operation, 1.6 × rated power is available for 2 s and 1.5 × for 10 s. The user manual sets separate limits for motor, non-linear and unbalanced loads (direct-on-line motor loads up to 1/10 of rated power), so the backup circuit loads should be checked during design.
- Switchover takes less than 10 ms with a single inverter and less than 20 ms in a parallel system.
- The generator input accepts up to 30–60 kW depending on the model; the datasheet also highlights flexible control for weak-grid and generator-hybrid operation.
Grid connection
- Issued certificates: EN 50549-1 / EN 50549-10 (TÜV Rheinland) and EN 62109-1/-2. Any further compliance required for a specific grid connection approval is checked against the manufacturer's documentation during design.
Related services and products
- C&I solar inverters – the full category
- C&I energy storage – battery energy storage systems
- Industrial batteries – batteries for hybrid inverter systems
- Design and installation – solar-plus-storage system sizing, installation and commissioning
- Monitoring and optimization – monitoring and energy management setup
- Industrial energy management – demand management, export prevention and tariff optimization
- Solis S6-GC string inverter
Energom Electronic Kft. is an official distributor of Solis. Services across the Central and Eastern European region; product delivery across Europe. Energom handles hybrid inverter and battery bank sizing, generator and grid connection design, installation, commissioning and energy management configuration.
FAQ
How many Solis S6-EH3P inverters can be paralleled?
Up to six units of the same model can be paralleled without a Solis STS cabinet; according to the manufacturer's manual, 7–10 units of the same model require an STS cabinet, for up to 600 kW, and each inverter needs its own battery. In a parallel system, switchover to backup operation takes less than 20 ms.
Which batteries work with the Solis S6-EH3P hybrid inverter?
The Solis S6-EH3P works with high-voltage Li-ion batteries in the 150–800 V range, on two independent ports with CAN communication; max charge and discharge current is 80 A (30–50 kW) or 84 A (60 kW) per port.
Can a generator be connected to the Solis S6-EH3P?
The Solis S6-EH3P has a dedicated generator input that accepts up to 30, 40, 50 or 60 kW depending on the model, on a 3/N/PE, 220/380 V or 230/400 V system.
What is the efficiency of the Solis S6-EH3P?
The Solis S6-EH3P max efficiency is 97.7% and European efficiency is 97.3%. Battery charging efficiency is up to 98.5% from PV and up to 97.8% from AC; battery discharge efficiency is 97.5%.
Request a quote
When requesting a quote, include the PV array power and string layout, the planned battery capacity and voltage, the loads to be supplied in backup operation, any generator rating and your grid connection details.
We respond within 24 hours on business days.