Key specifications at a glance

  • Output: −43 to −58 VDC adjustable (default −54.0 VDC); max 3000 W / 60 A (3000B), max 3050 W / 63.5 A (3000E)
  • Peak efficiency: 96.2% (DPR 3000B); 98.0% (DPR 3000E)
  • Input voltage: 90–300 VAC, derating at 176 VAC or below (3000B); 80–300 VAC, derating below 180 VAC (3000E)
  • Operating temperature: −40 to +75 °C; derating above +55 °C
  • Dimensions, weight: 84 × 41 × 265 mm (W × H × D); 1.3 kg (3000B), 1.4 kg (3000E)

Applications

  • Network base stations, cell sites and related mobile network equipment running on 48 VDC.
  • Fixed-line networks: telecom, access-network and broadband systems.
  • −48 VDC power for data communications and transmission equipment.
  • DC power systems built from rectifier modules operating in parallel, with modules replaceable during operation.

DPR 3000 EnergE models

DPR 3000 EnergE models
Model Rated output Distinguishing feature
DPR 3000B EnergE (ordering model: ESR-48/60A A) max 3,000 W / 60 A 96.2% peak efficiency; 90–300 VAC input; ORION control and monitoring
DPR 3000E EnergE max 3,050 W / 63.5 A 98.0% peak efficiency; 80–300 VAC input; withstands 415 VAC for max 10 minutes

48 V rectifier module specifications

48 V rectifier module specifications
Parameter DPR 3000B EnergE DPR 3000E EnergE
Design single-phase, hot-pluggable, fan-cooled single-phase, hot-pluggable, fan-cooled
AC input voltage range 90–300 VAC 80–300 VAC
Nominal input voltage, frequency 230 VAC; 45–66 Hz 230 VAC; 45–66 Hz
Input derating at 176 VAC or below below 180 VAC
Input overvoltage withstand not stated max 415 VAC for max 10 minutes, non-destructive
Power factor, THD PF > 0.99; THD < 5% PF > 0.99 and THD < 5% at 50% load or higher
Output voltage −43 to −58 VDC adjustable, default −54.0 VDC −43 to −58 VDC adjustable, default −54.0 VDC
Output power, current (at nominal input voltage) max 3,000 W / 60 A max 3,050 W / 63.5 A
Peak efficiency (load point not stated) 96.2% 98.0%
Power density 56.8 W/in³ 56.8 W/in³
Load regulation max ±250 mV max ±250 mV
Output ripple max 150 mVpp and < 55 mV RMS max 200 mV above 20% load
Current sharing within ±5% within ±5%
Communication, indications CAN bus; ORION control and monitoring; local indications: normal operation, low load, communication status CAN bus; local indications: normal operation, low load, communication status
Dimensions (W × H × D) 84 × 41 × 265 mm 84 × 41 × 265 mm
Weight 1.3 kg 1.4 kg
Operating temperature −40 to +75 °C, derating above +55 °C −40 to +75 °C, derating above +55 °C
Relative humidity 0–95%, non-condensing 0–95%, non-condensing
Altitude max 4,000 m max 4,000 m
Acoustic noise not stated max 50 dBA
MTBF not stated > 500,000 hours at 25 °C
Compliance not stated CE, CB, IEC/EN 60950-1, EN 55022, EN 300 386, RoHS

Source: Delta manufacturer product page (EMEA), November 2026. Specifications are subject to change by the manufacturer.

How to choose

Efficiency and heat load

The DPR 3000E reaches 98.0% peak efficiency, the DPR 3000B 96.2%. At sites running around the clock, higher efficiency means less waste heat and a lower cooling load. Delta does not state the load point for peak efficiency, so actual losses should be calculated at the expected load.

Utility supply quality

At sites with weak or fluctuating grid supply, the DPR 3000E operates from 80 VAC, derates below 180 VAC and withstands a 415 VAC input for up to 10 minutes without damage. The DPR 3000B covers 90–300 VAC and starts derating at 176 VAC or below.

Monitoring and system integration

Both models communicate over CAN bus. Delta's description of the DPR 3000B explicitly names ORION control and monitoring. The DPR 3000E page lists CAN bus communication only; confirm controller compatibility when requesting a quote.

Output quality

The two ripple figures are stated under different conditions: DPR 3000B max 150 mVpp and < 55 mV RMS; DPR 3000E max 200 mV above 20% load. For sensitive transmission loads, the two values are not directly comparable.

Operating environment

Both models operate from −40 to +75 °C, with derating above +55 °C, at altitudes up to 4,000 m. In outdoor cabinets that may run above +55 °C, plan spare module capacity to cover the derating.

Related services and products

Energom Electronic Kft. is an official distributor of Delta Electronics. Services across the Central and Eastern European region; product delivery across Europe. For 48 VDC systems built on DPR 3000 EnergE modules, Energom handles load and module-count sizing, installation, commissioning and maintenance.

FAQ

What is the difference between the DPR 3000B and the DPR 3000E?

The DPR 3000B delivers up to 3,000 W / 60 A from a 90–300 VAC input, with ORION monitoring; its peak efficiency is 96.2%. The DPR 3000E delivers up to 3,050 W / 63.5 A from an 80–300 VAC input and withstands a 415 VAC input for up to 10 minutes; its peak efficiency is 98.0%. Delta does not state the load point for peak efficiency.

What output voltage does the DPR 3000 EnergE provide?

Both Delta DPR 3000 EnergE models provide an output adjustable from −43 to −58 VDC, with a factory default of −54.0 VDC, matching −48 VDC telecom systems.

What is the operating temperature range of the DPR 3000 EnergE?

The Delta DPR 3000 EnergE modules operate from −40 to +75 °C; above +55 °C, output power is reduced (derating). Relative humidity can be 0–95%, non-condensing.

How large is a DPR 3000 EnergE module?

Both models measure 84 × 41 × 265 mm (W × H × D); the DPR 3000B weighs 1.3 kg and the DPR 3000E 1.4 kg.

Request a quote

When requesting a quote, include the DC load (A or kW), the required redundancy, the site's utility supply and operating temperature, any existing controller or system, and the battery backup time.

Request a Quote

We respond within 24 hours on business days.

Request a Callback